34 • Operations Smart Cabinet Distribution Unit
Installation and Operations Manual
Setting the tower AC voltage type:
The Set Tower 3phase command is used to set the product input AC voltage type.
NOTE: If set at the factory, the voltage type WILL NOT be user-editable.
To set the tower AC voltage type:
At the Smart CDU: prompt, type set tower 3phase, followed by the absolute tower name and yes or no.
Press Enter.
Example
The following command sets the AC voltage type for tower .A to non-3-phase:
Smart CDU: set tower 3phase.a no<Enter>
Displaying tower information:
The Show Towers command displays information about the Sentry. This information includes the
absolute and descriptive Sentry names, serial and model numbers, and voltage types.
To display tower information:
At the Smart CDU: prompt, type show towers and press Enter.
Example
Smart CDU: show towers<Enter>
Tower ID: .A
Name: TowerA
Product S/N: AA06F011157
Model No.: CS-24V2-C20
3-Phase: No
Power Type: AC
More (Y/es N/o):
Environmental Monitor Administration
Creating a descriptive Environmental Monitor name:
The Set Envmon Name command assigns a descriptive name to the integrated Environmental Monitor.
This descriptive name is displayed when the Evnmon command is issued.
To create an Environmental Monitor name:
At the Smart CDU: prompt, type set envmon name followed by the absolute environmental monitor
name, then a descriptive name of up to 24 alphanumeric and other typeable characters - (ASCII 33 to
126 decimal) are allowed; spaces are not allowed. Press Enter.
Example
The following command adds the descriptive name Florida_HQ_1to the Environmental Monitor:
Smart CDU: set envmon name .a Florida_HQ_1<Enter>
Creating a descriptive temperature/humidity sensor name:
The Set Envmon THS Name command assigns a descriptive name to a temperature/humidity sensor.
This descriptive name is displayed when the Evnmon command is issued.
To create a temperature/humidity sensor name:
At the Smart CDU: prompt, type set envmon ths name followed by the absolute name of the
temperature/humidity sensor, then a descriptive name of up to 24 alphanumeric and other typeable
characters - (ASCII 33 to 126 decimal) are allowed; spaces are not allowed. Press Enter.
Example
The following command adds the descriptive name T/H2_Florida_HQ_1 to the second
temperature/humidity sensor:
Smart CDU: set envmon ths name .a2 T/H2_Florida_HQ_1<Enter>